Table 310.15(B)(16)

SizeCopperAluminum
60°C75°C90°C60°C75°C90°C
18 AWG14
16 AWG18
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480
1,000 kcmil455545615375445500
1,250 kcmil495590665405485545
1,500 kcmil525625705435520585
1,750 kcmil545650735455545615
2,000 kcmil555665750470560630

Allowable ampacities of insulated conductors rated up to 2,000V in raceway, cable, or earth — not more than three current-carrying conductors, ambient temperature 30°C (86°F). THWN / THHN / XHHW.

Source: NEC 2020 Table 310.16. Values in amperes.