Conductor Adjustment Factors

NEC 2020 — Table 310.15(C)(1)

Number of conductorsPercent of adjusted ampacity
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

For one to three current-carrying conductors, no adjustment factor is applied. Count conductors as required by the applicable code rules.

Source: NEC 2020 Table 310.15(C)(1). Verify requirements against the locally adopted code and applicable amendments.